CYRUSX
← Tools

Electrical Engineering

Wire Gauge / AWG

Look up AWG wire specifications — diameter, resistance, ampacity ratings, and NEC circuit breaker requirements for copper conductors.

2.053 mm

Diameter

3.3100 mm²

Cross-section

5.211 Ω/km

Resistance

20 A

Free-Air Ampacity

NEC Circuit Guide — AWG 12

Max 20A circuit breaker per NEC 310.12 / 240.4(D) for copper in conduit (60°C terminals).

20A circuits — kitchen, bathroom, garage outlets

✓ NEC 240.4(D) explicitly caps AWG 12 at 20A — the breaker must not exceed this even if the terminal rating would allow more.

20A

Max Breaker

In Conduit / Enclosed

20 A

Wires bundled or run through conduit, walls, or enclosures. Heat can't escape freely — lower ampacity. This is the NEC table value used for home and building wiring.

Free Air / Chassis

20 A

Single wire in open air, or internal wiring of equipment (control panels, appliances, machines). Better heat dissipation allows higher current. Not for branch circuit breaker sizing.

Why two ampacity ratings? Ampacity drops when wires are enclosed because heat builds up. NEC Table 310.12 gives the lower conduit values used for sizing breakers in home and commercial wiring.
Quick example: A 12 AWG wire on a 20A breaker is correct — NEC limits 12 AWG to 20A in conduit. Installing it on a 30A breaker would be a code violation and a fire hazard.

Full AWG Reference

Click any row to select. Copper conductors, 60°C insulation rating.

AWGDiameterAreaResistanceIn ConduitFree AirMax Breaker
AWG 08.25153.48000.322125 A150 A125 A
AWG 26.54433.62000.51395 A95 A95 A
AWG 45.18921.15000.81570 A70 A70 A
AWG 64.11513.30001.29655 A55 A55 A
AWG 83.2648.36702.06140 A40 A40 A
AWG 102.5885.26103.27730 A30 A30 A
AWG 122.0533.31005.21120 A20 A20 A
AWG 141.6282.08108.28615 A15 A15 A
AWG 161.2911.309013.17013 A13 A10 A
AWG 181.0240.823120.95010 A10 A7 A
AWG 200.8120.517633.3105 A7.5 A
AWG 220.6440.325552.9603 A5 A
AWG 240.5110.204784.2202 A3.5 A
AWG 260.4050.1288133.9001 A2.2 A
AWG 280.3210.0810212.9000.5 A0.8 A
AWG 300.2550.0509338.6000.3 A0.5 A

Ampacity per NEC Table 310.12 for copper conductors with 60°C-rated terminals, not more than 3 current-carrying conductors in conduit or raceway. Always consult a licensed electrician and your local AHJ (Authority Having Jurisdiction) before any wiring installation.